Case: T09FR00067

Parcel: 11613193E

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/04/2009 INSP - FULL Approved
01/08/2009 INSP - FULL Correction Required DURING THE LAST SPRINKLER INSPECTION, NOV. 2008, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE

1) RADIATION THERAPY - IN THE ELECTRICAL ROOM EQUIPMENT WAS INSTALLED THAT WILL IMPEDE THE PERFORMANCE OF THE FIRE SPRINKLER. THE PANEL NEEDS TO BE REINSTALLED FOR THE SPRINKLER TO OPERATE CORRECTLY

2) PRESSURE QUAGES AT THE SPRINKLER RISER ARE PAST 5 YEARS OLD. THEY SHALL BE REPLACED OR RECALIBRATED

3) BY THE NORTH WEST EXIT THERE IS A STORE ROOM THAT HAS BEEN BUILT AND IT DOES NOT HAVE THE REQUIRED SPRINKLER COVERAGE. SPRINKLERS SHALL BE ADDED