Case: T09FR00049

Parcel: 12314007B


Addresses:

2001 N PARK AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00049

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2009 INSP - FULL Approved RELOCATED THE PULL STATION
01/13/2009 INSP - FULL Violation 2006 IFC 901.6
MOVE PULL STATION NEXT TO THE EXIT DOOR. THE WET SYSTEM CURRENTLY INSTALLED IS OKAY AS LONG AS IT CAN BE SERVICED AND IN WORKING CONDITION.
01/07/2009 INSP - FULL Correction Required Report from Sun Devil Fire (attached to printout in complaint log) says the pull system is not by an exit, conduit/service lines are not sealed, and system is not UL300.