Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR00016
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2009 | INSP - FULL | Approved | ||
01/05/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR INVOICE SHALL BE PROVIDED THE FIRE PREVENTION OFFICE. 1) SAGUARO PHYSICIANS - PHONE ROOM,THE CORRODED, DUE TO A LEAK, SPRINKLER HEAD SHALL BE REPLACED 2) SAGUARO PHYSICIANS FILE STORE ROOM - A SPRINKLER HEAD EXCEEDS THE ALLOWABLE DISTANCE OF 7' 6 INCHES OFF A WALL. 3) KING AND FIRSCH - FILE STORAGE ROOM HAS A SPRINKLER THAT EXCEEDS THE ALLOWABLE DISTANCE OF 7' 6 INCHES OFF A WALL AND ANOTHER IN THE OFFICE BEING USED AS A STORAGE AREA 4) PROVIDE A RESTRICTED ORIFICE AT THE TEST DRAIN |