Case: T09FR00016

Parcel: 12108309A


Addresses:

6226 E PIMA ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/20/2009 INSP - FULL Approved
01/05/2009 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR INVOICE SHALL BE PROVIDED THE FIRE PREVENTION OFFICE.

1) SAGUARO PHYSICIANS - PHONE ROOM,THE CORRODED, DUE TO A LEAK, SPRINKLER HEAD SHALL BE REPLACED

2) SAGUARO PHYSICIANS FILE STORE ROOM - A SPRINKLER HEAD EXCEEDS THE ALLOWABLE DISTANCE OF 7' 6 INCHES OFF A WALL.

3) KING AND FIRSCH - FILE STORAGE ROOM HAS A SPRINKLER THAT EXCEEDS THE ALLOWABLE DISTANCE OF 7' 6 INCHES OFF A WALL AND ANOTHER IN THE OFFICE BEING USED AS A STORAGE AREA

4) PROVIDE A RESTRICTED ORIFICE AT THE TEST DRAIN