Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR00014
Inspection Description - INSP - FULL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 1-5-2009, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 2550 E. RIVER. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 01/05/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICEINCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE COMPLETED REPAIR ORDER SHALL BE FORWARDED TO THE FFIRE PREVENTION OFFICE. 1) THE SPARE HEAD BOX SHALL HAVE THE REQUIRED SPECIAL WRENCH FOR REPLACING THE TY3231 SPRINKLERS 2) THE RISER GUAGES ARE 5 YEARS OLD. THEY SHALL BE REPLACED OR RECALIBRATED. |