Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02811
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/24/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/21/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING FIXTURES 2) MISSING PLUMBING BATHROOMS 3) FINISH #1, 6 & 11 PREVIOUS INSPECTION 4) UNIT IS NOT HABITABLE |
|
12/31/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SECURE CONDUIT AND BOXES TO CARPORT WALL 2) GROUNDED RECEPTS ON UNGROUNDED CIRCUITS 3) KITCHEN RECEPTS TO BE GFCI PROTECTED 4) SUPPORT FIXTURES ABOVE GRID TYPE CEILING-USE APPROVED WIRING METHODS AND EXPOSED CONDUCTORS 5) PROTECT CABLE BEHIND WHERE RANGE WOULD BE 6) SMOKE DETECTORS NEEDED FOR BEDROOMS AND HALL 7) BATHROOM RECEPTS TO BE GFCI PROTECTED 8) MAINTAIN WORKING CLEARANCE IN FRONT OF SUB PANEL 9) REATTACH GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 10) RE-ATTACH GAS AND WATER BONDS 11) PROPERLY TERMINATE GROUNDED AND GROUNDING CONDUCTORS AT MAIN DISCONNECT 12) OUTDOOR RECEPTS TO BE FOR WET LOCATION 13) EXPOSED CONDUCTORS AND CABLES BACK PORCH 14) FILL UNUSED OPENING IN SUB PANEL BACK AND COVER |