Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/24/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SMOKE DETECTORS NOT INSTALLED PROPERLY TO BE MINIMUM 36" FROM VENT, IF INSTALLED ON WALL TO BE MINIMUM 4" DOWN AND NO MORE THAN 12" |
|
| 12/24/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED 2) BATHROOM RECEPTS TO BE GFI PROTECTED 3) INSTALL SMOKE DETECTORS IN BEDEROOMS AND HALL OUTSIDE BEDROOM 4) OUTDOOR RECEPTS TO BE GFI PROTECTED 5) OUTDOOR SWITCHES AND RECEPTS TO HAVE WEATHER PROOF COVERS 6) INSTALL MISSING WALL PLATES 7) BELL BOX AT PANEL TO BE SECURED 8) RESCHEDULE WHEN COMPLETE 9) NO RECONNECT ALLOWED-HAZARDOUS-NEED TO CORRECT ITEMS LISTED |