Permit: T09EL02771

Parcel: 135060810

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/05/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO HAVE WORKING KITCHEN SOUTH HOME IS HABITABLE TO GET POWER ON
2) KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED
3) INSTALL MISSING RECEPT PLATES
4) HAVE EXPOSED WIRING AT ROOF TOP UNIT
5) INSTALL GROUND RODS AT SERVICE PANEL
6) HOME IS NOT HABITABLE AT THIS TIME, NEEDS TO BE HABITABLE TO HAVE POWER RESTORED. ANOTHER OPTION IS TO OBTAIN PERMIT FOR GENERAL REPAIRS AND AHVE TEMP SERVICE ADDED TO PERMIT. WOULD NEED TO PUT GFI RECEPT AT PANEL AND DISCONNECT ALL BRANCH CIRCUITS INTO HOME