Permit: T09EL02751

Parcel: 123121910


Addresses:

1150 E GRANT RD #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL02751

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/28/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCEL PER RUBEN
04/09/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GUEST HOUSE:
1) EXPOSED WIRING IN KITCHEN AND CEILING FAN IN BEDROOM NOT WIRED TO CODE
2) SPOKE TO ELECTRICIAN IN MARCH TO SCHEDULE MEETING AT SITE, HE NEVER CALLED INSPECTION TO MEET AT SITE. RECALL INSPECTION AFTER CORRECTIONS ARE COMPLETE AT GUEST HOUSE
3) OK ROOF
04/07/2010 ELECTRIC - FINAL Cancelled IVRS - RI canceled
03/04/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NO CORRECTIONS COMPLETED PER PREVIOUS INSPECTION NOTES
2) USE QUALIFIED OR LICENSED ELECTRICIAN
3) LEFT MESSAGE AND PHONE NUMBER
4) A REINSPECTION FEE WILL BE ASSESSED NEXT INSPECTION IF NO COMPLIANCE
02/22/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
1. SEE NOTES 1 & 2 LAST INSPECTION
2. COULD NOT LOCATE LOCK BOX FOR GUEST HOUSE
3. ALSO A GROUNDING ELECTRODE SYSTEM IS NEEDED FOR GUEST HOUSE PER NEC 250.32
4. CALLED REALTOR, LEFT MESSAGE
02/16/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MULTI TAPS ON LUG IN SERVICE DISCONNECT NOT APPROVED METHOD, USE MULTI BARREL LUGS
2) SEE NOTE #7 LAST INSPECTION
3) UNIT #1 & 2 ON SAME SERVICE, WILL NEED ACCESS INTO #2 FOR INSPECTION, ALSO ADD TO THIS PERMIT
12/18/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE GROUNDING ELECTRODE HAS BEEN CUT, REINSTALL GROUNDING ELECTRODE SYSTEM PER 250-NEC
2) WIRING AT SUB PANEL NOT TO CODE, EXPOSED ROMEX AND BREAKERS MISSING
3) KITCHEN AND BATHROOM RECEPTS TO BE GFI PROTECTED
4) MISSING DEVICE COVER PLATE IN LIVING ROOM
5) INSTALL SMOKE DETECTOR IN HALLWAY
6) PROVIDE LADDER FOR ROOF INSPECTION
7) WATER HEATER VANDELIZED
8) PVC CONDUIT UNDER GROUND TO BOTTOM OF SERVICE DISCONNECT ? WHAT IS THIS FOR ?