Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02733
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) CLEAN SURFACE UNDER GROUND BAR 250.12 2) PROTECT CONDUCTORS AT FITTINGS 300.4 3) FILL UNUSED OPENING IN JUNCTION BOX 4) USE APPROVED MARKING TAPE FOR GROUNDED CONDUCTOR 5) PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
01/11/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
12/18/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO WORK PROGRESS-SERVICES ENERGIZED WITHOUT CLEARANCE 2) A REFEE MAY BE ASSESSED PER ADMIN CODES |
|
12/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A LISTED AND APPROVED MAST BRACE KIT IS NEEDED 2) BOND SERVICE RISER, GUTTER 3) SPLIT BOLT ONLY FOR 2 CONDUCTORS-A RING & A TAP 4) GROUNDING ELECTRODES TO BE DRIVEN AND FLUSH TO GRADE 5) USE APPROVED FITTINGS WITH L.B.'S 6) TIGHTEN LOOSE FITTINGS 7) RISER HARDWARE TO BE 1/4" MINIMUM 8) NO GENERAL LABELING-DIRECTORY TO BE AS PER 408.4 9) CORRECTLY IDENTIFY GROUDNING CONDUCTORS 250.119 10) ARE SERVICE CONDUCTORS MARKED "SUN LIGHT RESISTANT" 11) ADD OTHER ADDRESS TO PERMIT OR NEED OTHER PERMITS 12) GROUNDED CONDUCTOR TO BE INSULATED |