Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2010 | ELECTRIC - CABLE DROP | Approved | ||
| 05/11/2010 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) CHECK #5 & 6 NEXT INSPECTION |
|
| 04/07/2010 | ELECTRIC - CABLE DROP | Denied | 1) #8 + LARGER TO BE STRANDED IN RACEWAY 2) SPLIT BOLTS FOR ONLY A RUN + A TAP 3) PLANS CALL FOR A GROUNDED CONDUCTOR 4) NEED GROUNDING BONDS AS PER PLANS 5) LABELING IDENTIFICATION PER 230.2 (B) REQUIRED 6) NEED BETTER GROUND FAULT PATH A FIRE PUMP CONNECTION 250.97 7) VERIFY LISTING + LABELING OF JOCKEY PUMP CONTROLER ALSO SERVICE DISCONNECT LABELING |