Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/01/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/22/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) NO ONE ON SITE |
|
| 01/04/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) HIGHEST AVAILABLE BREAKER NOT OVER 6'-7" 3) BOND TO INTERIOR SIDE OF GAS PIPING 4) TIGHTEN CONDUCTOR TERMINATIONS 5) PLEASE VERIFY SUNLIGHT RESISTANT OF CONDUCTORS 6) LABEL CIRCUITS AS PER 408.4 7) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT 8) CABLE SHEATH TO ENTER ENCLOSURE AT LEAST 1/4" 9) TIGHTEN LOOSE FITTING 10) BOND JUNCTION BOX ENCLOSURE 11) SECURE CABLE TO BOX 312.5 |