Permit: T09EL02644

Parcel: 130083560


Addresses:

3407 E 28TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/02/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/01/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/22/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
There is no access to the site.| 920*
1) NO ONE ON SITE
01/04/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) A PERMANENT METAL ADDRESS LABEL IS NEEDED
2) HIGHEST AVAILABLE BREAKER NOT OVER 6'-7"
3) BOND TO INTERIOR SIDE OF GAS PIPING
4) TIGHTEN CONDUCTOR TERMINATIONS
5) PLEASE VERIFY SUNLIGHT RESISTANT OF CONDUCTORS
6) LABEL CIRCUITS AS PER 408.4
7) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT
8) CABLE SHEATH TO ENTER ENCLOSURE AT LEAST 1/4"
9) TIGHTEN LOOSE FITTING
10) BOND JUNCTION BOX ENCLOSURE
11) SECURE CABLE TO BOX 312.5