Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BONDING JUMPERS NOT SIZED PROPERLY NEC 250.102 AND 250.66 2) RESCHEDULE WHEN COMPLETE |
|
| 12/24/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL GROUNDING ELECTRODE SYSTEM 2) BOND GAS AND WATER PIPING 3) INSTALL MAIN BONDING JUMPER 4) NEED PANEL DIRECTORY 5) BOND OFF SET NIPPLE AND SERVICE RISER 6) SEAL OPENING AT BACK OF PANEL WHERE WIRES ENTER WITH NON COMBUSTIBLE MATERIAL |