Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/08/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GEC MUST BE BONDED TO DISCONNECT, ENCLOSE ALSO WATER AND GAS PIPING 2) ALSO APPLY A FIRE PROOF SEALANT WHERE FEEDERS PASS THRU WOOD BACK BOARD |
|
| 12/03/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UNITS NOT GROUNDED AT SERVICE, INSTALL GROUNDING ELECTRODE SYSTEM PER NEC 250 2. MUST HAVE 36" IN FRONT OF SERVICE EQUIPMENT WORKING CLEARANCE, TRIM BACK BUSH. |