Permit: T09EL02632

Parcel: 11207069C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/09/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/08/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/15/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GEC MUST BE BONDED TO DISCONNECT, ENCLOSE ALSO WATER AND GAS PIPING
2) ALSO APPLY A FIRE PROOF SEALANT WHERE FEEDERS PASS THRU WOOD BACK BOARD
12/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. UNITS NOT GROUNDED AT SERVICE, INSTALL GROUNDING ELECTRODE SYSTEM PER NEC 250
2. MUST HAVE 36" IN FRONT OF SERVICE EQUIPMENT WORKING CLEARANCE, TRIM BACK BUSH.