Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/03/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/01/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN RECEPT TO BE GFCI PROTECTED 2) OPEN SPLICES IN WALL-GARAGE 3) PROTECT NM CABLES IN GARAGE 4) WIRING TO SIDE OF PANEL NOT TO CODE 5) BREAKER AMPCITY TO MATCH CONDUCTOR SIZE 6) 40 AMP DISCONNECT IN LAUNDRY COMING OFF OF WALL. WHAT DOES IT SUPPLY ? 7) FILL UNUSED OPENINGS IN PANEL |