Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER CROSSOVER |
|
| 10/20/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ANSWER FRONT DOOR 8:10 AM |
|
| 10/18/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE GROUND RODS FOR INSPECTION 2) BLANK COVER UNUSED OPENINGS 3) PROVIDE SECONDARY GROUND ROD MINIMUM 6' APART 4) 40 AMP WHITE HOT LEAD MUST BE RED OR BLACK |