Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2009 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/25/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THIS IS SERVICE UPGRADE AND PERMIT TO BE REVISED ACORDINGLY 2) SERVICE CONDUCTORS NOT SIZED PROPERLY FOR 200 AMP SERVICE 3) BOND NIPPLE AND RISER PER NEC 250.92 4) NEED TO PROTECT CONDUCTORS #4 AND LARGER FROM PHYSICAL DAMAGE AT EXIT FROM RACEWAYS, NIPPLES AND CONDUCTORS 5) INSTALL NEW GROUNDING ELECTRODE SYSTEM. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS 6) INSTALL MAIN BONDING JUMPER 7) INSTALL PROPER CONNECTOR AT LB ENTRY TO PANEL 8) INSTALL PROTECTIVE BUSHING AT WIRE ENTRY AND SEAL OPENING WITH NON COMBUSTIBLE MATERIAL 9) NEED PANEL DIRECTORY 10) BOND METAL GAS AND WATER PIPING TO SERVICE 11) STRAP EMT TO WITHIN 3' OF PANEL 12) RESCHEDULE WHEN COMPLETE |