Permit: T09EL02579

Parcel: 136242800


Addresses:

7042 E 42ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T09EL02579

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
11/25/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS IS SERVICE UPGRADE AND PERMIT TO BE REVISED ACORDINGLY
2) SERVICE CONDUCTORS NOT SIZED PROPERLY FOR 200 AMP SERVICE
3) BOND NIPPLE AND RISER PER NEC 250.92
4) NEED TO PROTECT CONDUCTORS #4 AND LARGER FROM PHYSICAL DAMAGE AT EXIT FROM RACEWAYS, NIPPLES AND CONDUCTORS
5) INSTALL NEW GROUNDING ELECTRODE SYSTEM. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS
6) INSTALL MAIN BONDING JUMPER
7) INSTALL PROPER CONNECTOR AT LB ENTRY TO PANEL
8) INSTALL PROTECTIVE BUSHING AT WIRE ENTRY AND SEAL OPENING WITH NON COMBUSTIBLE MATERIAL
9) NEED PANEL DIRECTORY
10) BOND METAL GAS AND WATER PIPING TO SERVICE
11) STRAP EMT TO WITHIN 3' OF PANEL
12) RESCHEDULE WHEN COMPLETE