Permit: T09EL02578

Parcel: 140373590

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/12/2010 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
12/16/2009 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1) 15 DAY RECONNECT IS ALLOWED
2) STILL NEED TO CORRECT ITEMS FROM 12/11/09-IF NOT CORRECTED WITHIN 15 DAYS POWER WILL BE SHUT OFF
12/11/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RECEPTACLE IN CARPORT TO BE GFI PROTECTED.
2) RECEPTACLE/SWITCH IN CARPORT TO HAVE WEATHER PROOF COVER
3) ROMEX CABLE IN CARPORT TO BE PROTECTEDFROM PHYSICAL DAMAGE AND NOT TO BE INSTALLED IN WET LOCATION.
4)PROPERLY WIRE LIGHT FIXTURE IN CARPORT
5) INSTALL DEAD FRONT ON A SERVICE PANEL & INSTALL WEATHER PROOF COVER.
6) LABEL CIRCUITS
7) SEAL OPEN KNOCKOUTS BOTTOM SERVICE PANEL
8) INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS.
NO RECONNECT HAZARDOUT. COMPLETE ITEM #5 FOR 15 DAY RECONNECT.
12/02/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RECEPTACLE IN CARPORT TO BE GFI PROTECTED
2) RECEPTACLE SWITCH IN CARPORT TO HAVE WEATHERPROOF COVERS
3) ROMEX CABLE IN CARPORT TO BE PROTECTED FROM PHYSICAL DAMAGE & TO BE INSTALLED IN WET LACATIA
4) PROPERLY WIRE LIGHT FIXTURE IN CARPORT
5) ROMEX, CABLE & PANEL TO BE PROTECTED FROM PHYSICAL DAMAGE NOT TO BE INSTALLED IN WET LOCATION.
6) REMOVE NON WIDE COMPLIANT SUB PANEL & WIRING TO PATIO AREA
7) REMOXE EXTENDSION CORD FROM UNDERGROUND & SOUTH EAST CORNER
8) INSTALL MISSING DEED TRUST & PANEL AND LABEL CIRCUITS
9) INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS
10) RESCHEDULE WHEN READY.