Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T09EL02567
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
12/16/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) ONLY ONE NEUTRAL TO LUG TERMINATION 200.8 2) TIGHTEN LOOSE FITTINGS AT LB'S 3) BREAKERS TO BE LISTED FOR USE BY MANUFACTURES 4) LABEL ALL BREAKERS |
|
12/03/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER CROSS OVER 2) RISER HARDWARE TO BE 1/4" MINIMUM 3) MAINTAIN WORKING CLEARANCES AT SUB PANEL 110.26 |