Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/11/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* *NOTED FRAME INTERIOR OBSERVED EXPOSED CONDUCTORS INSIDE OF STRUCTURE 1). USE APPROVED & LISTED MAST BRACE KIT FOR RISER 2). SPLIT BOLTS LISTED FOR ONLY 2 CONDUCTORS - A RUN & A TAP 3: LISTED BONDING DEVICES NEEDED ON SERVICE SUPPLIES & RISER 250.92 4) BOND JUNCTION BOX ENCLOSER |