Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/25/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/24/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROPERLY INSTALL WIRING TO RECEPTACLE AT FRONT PORCH OR REMOVE. OUTDOOR RECEPTS TO BE GFI PROTECTED (CHECK ALL) 2) INSTALL WIRING TO DRYER PER CODE. SEAL TIGHT TO BE PROTECTED FROM PHYSICAL PROTECTION OR REMOVED 3) PVC TO SPA AT BACK PORCH TO BE SCHEDULE 80 AND INSTALLED PER CODE OR REMOVED 4) SEAL OPEN KNOCK AT PANEL 5) REMOVE NON CODE COMPLIANT TAP AT SERVICE PANEL 6) KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED 7) BATHROOM RECEPTACLE TO BE GFI PROTECTED 8) INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS 9) RESCHEDULE WHEN COMPLETE |
|
| 11/23/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) CALLED AND LEFT MESSAGE 2) PROPERTY LOCKED 3) NEED ACCESS TO INTERIOR OF HOME 4) NEED TO RESCHEDULE 10:45 AM |