Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09EL02546

Parcel: 126134330


Addresses:

4533 E DOUGLAS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL02546

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/08/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL NEUTRAL CONDUCTOR AND EQUIPMENT GROUND TO 30 AMP SUB PANEL
2) NEUTRALS TO BE IDENTIFIED ALONG ENTIRE LENGTH
3) GROUNDS TO BE IDENTIFIED ALONG ENTIRE LENGTH
4) CANNOT USE GREEN CONDUCTORS AS HOTS OR NEUTRALS
5) USE #10 CONDUCTORS TO DRYER CIRCUIT
6) PROPERLY INSTALL SEAL TIGHT TO 30 AMP SUB PANEL, USE LISTED SEAL TIGHT CONNECTIONS
7) ARE ALUMINUM AND COPPER CONDUCTORS SPLICED TOGETHER ? THERE ARE DISIMILAR METALS AND CANNOT BE SPLICED TOGETHER
8) CANNOT USE TEK SCREW FOR CONNECTION OF GROUND
9) ALL STRANDS OF WIRES TO BE UNDER LUGS
11/20/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NOTES FOR BOTH UNITS:
1) GROUNDING, BONDING, SERVICE WIRES AND RISER OK
2) NEED TO SEE BRANCH CIRCUITS LANDED
3) CALL BACK FOR FINAL