Permit: T09EL02535

Parcel: 136251190


Addresses:

6609 E MARY DR

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/24/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED PANEL DIRECTORY
2) FINISH WIRING TO A/C UNIT
3) SEAL OPENING AT WIRE ENTRY WITH NON-COMBUSTIBLE MATERIAL
4) MARK "SERVICE DISCONNECT"
11/23/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL. HAVE BROKEN RETAINING CLIP FOR BREAKER FOR NEW A/C UNIT
2) INSTALL PROPER WIRING METHOD TO NEW CONDENSING UNIT. CANNOT USE MC CABLE OUTDOORS
3) INSTALL PROPER OVERCURRENT PROTECTION ON WIRING TO A/C UNIT, NEED SERVICE RECEPT AT CONDENSING UNIT
4) INSTALL ROOF JACK AT ROOF PENETRATIONS
11/20/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED PROPER BRAND BREAKER AND BREAKER SIZE
2) NEED ADDRESS LABEL ON METER BASE
3) NEED CONNECTOR FOR GROUNDING ELECTRODE ON BOTTOM OF PANEL AND MC NEEDS TO BE STRAPPED
4) SHOULD PUT NEW SERVICE
11/19/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPLAIN MC CABLE LEAVING PANEL GOING UP ONTO ROOF
2) NEED PLANS AND PERMITS FOR ALL NEW WORK
3) HAVE INSTALLED NEW DRINKING FOUNTAIN ON REAR OF HOME
4) POWER WILL NOT BE RELEASED TO POWER COMPANY UNTIL PERMITS OBTAINED FOR ALL NEW WORK
5) CONSTRUCTION DEBRIS IS PILED IN DRIVEWAY. HOUSE IS NOT OCCUPIED