Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
07/07/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/17/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO RECONNECT-HAZARDOUS
2) POST HOUSE NUMBERS VISIBLE FROM STREET
3) 2 BEDROOMS ADDED TO SOUTH END POSSIBLE ENCLOSURE OF EXISTING CARPORT AND STORAGE, LAUNDRY MISSING OUTLETS PER CODE
4) MISSING SMOKE ALARMS ALL BEDROOMS AND HALLWAYS
5) 2 WIRE OUTLETS AND WIRE WITH GROUND MIXED THROUGHOUT 60 AMP SECURE 2 WIRE
6) GFCI PROTECT KITCHEN COUNTER OUTLETS
7) WATER HEATER REQUIRES COMBUSTION RELIEF
8) SECURE DISHWASHER DRAIN HOSE AT HIGHEST POINT
HAZARDOUS ELECTRICAL:
1) RISER NEEDS TO BE SECURED, SHIFTED 20 DEGREES
2) 60 AMP SERVICE HAS BEEN OVERLOADED, ADDITION OF 8 20 AMP BREAKERS IN SUB PANEL IN LAUNDRY ROOM
3) SUB PANEL ETRANCE NOT TO CODE/NOT GROUNDED
4) ADDITION 220 TO LAUNDRY ROOM
5) SEAL KNOCKOUTS PANEL
6) EXPOSE ALL ELECTRICAL WORK DONE WITHOUT INSPECTION OR HAVE LICENSED ELECTRICIAN VERIFY ON LETTER HEAD ALL WORK DONE TO CODE
7) ADDED 20 AMP DISCONNECT BREAKER IN SQUARE D TO MURRAY SUB PANEL
8) DUE TO OVER LOADED PANEL UPGRADE REQUIRED