Permit: T09EL02507

Parcel: 13017149A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL02507

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/21/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/18/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH PREVIOUS INSPECTION ITEMS ON 11/17/09
11/17/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED PLANS AND PERMIT FOR INSTALLE OF NEW SERVICE
2) INSTALL FUSES AT SERVICE
3) HAVE 2 WIRES TERMINATED AT LUG LISTED FOR 1 WIRE TERMINATION AT SERVICE DISCONNECT
4) REMOVE MAIN BONDING JUMPER AT PANEL
5) PROVIDE 6' LADDER FOR INSPECTION
6) PROVIDE ACCESS TO ROOF
7) PANEL TO BE PROPERLY SECURED
8) NO MOREN THAN 1/8" GAP AROUND PANEL