Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) ITEMS ON LIST OK |
|
| 12/15/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FINISH DRIVING GROUND ROD FLUSH WITH GRADE 2) NEED GAS BOND 3) MAIN BREAKER NEEDS MANUFACTURE HOLDOWN 4) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICE 5) BOND SERVICE NIPPLE 6) INSTALL MAIN BONDING JUMPER |