Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/31/2009 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) LOCKED AND NO ANSWER AT DOOR |
|
| 12/30/2009 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* 1) EXPOSED WIRING NEEDS TO BE IN RACEWAY 2) CALL FOR FINAL AFTER TEP TIE IN TO INSPECT OLD SERVICE CHANGE OUT 3) CALLED INTO OFFICE |
|
| 11/17/2009 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE A LISTED RISER BRACE, HOMEMADE BRACE OUT OF EMT CONDUIT NOT ALLOWED 2) USE APPROVED J-BOX FOR LOAD CONNECTIONS, OLD INDOOR RATED DISCONNECT NOT APPROVED 3) INSTALL PERMANENT ADDRESS LABEL ON SERVICE EQUIPMENT 4) USE PROPER STRAP FOR RISER CONDUIT, OVER SIZE 2-HOLE STRAP WITH WOOD SPACERS NOT APPROVED |