Permit: T09EL02492

Parcel: 135081520


Addresses:

7310 E 28TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/03/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) COMPLETE ITEM #2 FROM PREVIOUS INSPECTION
11/23/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO OBTAIN PERMITS FOR ALL NEW WORK
2) CANNOT EXIT TOP END WALL. DO NOT RUN BRANCH CIRCUITS IN BARRIER SECTION
3) NEUTRAL CONDUCTORS TO BE IDENTIFIED ALONG ENTIRE LENGTH
4) EQUIPMENT GROUNDS TO BE SPLICED PROPERLY, USE WIRE NUTS OR CRIMPS
5) PROPERLY INSTALL BONDING JUMPER TO BOND BUSHING
6) THIS PROPERTY ALREADY HAS RECONNECT PERMIT THAT WAS NEVER FINALED. NEED TO COMPLY WITH RECONNECT INSPECTION REQUIREMENTS
7) ONCE PERMIT IS OBTAINED FOR ALL NEW WORK, INSTALL GFI RECEPT AT PANEL. DISCONNECT ALL BRANCH CIRCUITS FOR TEMP CONSTRUCTION POWER