Permit: T09EL02486

Parcel: 120077460


Addresses:

519 W DISTRICT ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/10/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/09/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS TO GROUNDING ELECTRODE, ALSO 2ND GROUND ROD NEEDED 6' MINIMUM
2) BOXES MORE THAN 1/4" BOX TO SURFACE OR MORE THAN 1/8" SIDES
3) FILL UNUSED OPENINGS IN BOXES
4) ONLY ONE CONDUCTOR TO ACORN CLAMP
5) NEED WATER BOND
6) FINISH PAD
7) NEED CORRECT SIZE RISER STRAP
8) WORKING WITH GUS MAUGHAN
12/04/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) WORK DONE IS NOT TO CODE
2) A REFEE MAY BE ASSESSED IF WORK NOT COMPLETED PER ADMINISTRATION CODES
12/02/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
11/16/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) HIGHEST BREAKER 6'-7"
2) SUPPORT RISER ABOVE PANEL
3) USE APPROVED LISTED MAST BRACE KIT
4) PLEASE VERIFY GROUND RODS
5) NM CABLE TO PANEL HAS BEEN RECENTLY INSTALLED WITHOUT INSPECTIONS
6) VERIFY GAS AND WATER BONDING