Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/10/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING SMOKE DETECTORS 2) GROUNDED RECEPTS ON UNGROUNDED CIRCUITS 3) MISSING COVER SCREWS 4 OUTLET BOX 4) DEVICE IN COMBUSTIBLES-SWITCH 314.20 5) USE APPROVED ELECTRICAL FITTINGS 6) FILL UNUSE OPENING IN COVERS WITH APPROVED PARTS |