Permit: T09EL02456

Parcel: 118035440


Addresses:

1328 S CURLEY WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/14/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) SEALING LOCK NUT NEEDED AT SERVICE NIPPLE ALSO
12/10/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOND SERVICE NIPPLE 250.92
2) NEED TO SEE CABLE ENTERING BACK OF PANEL
3) NO GENERAL LABELING OF CIRCUITS 408.4
4) ANTI-OXIDE COMPOUND NEEDED FOR ALUMINUM CONDUCTORS
5) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICE
6) MAINTAIN WIRE BENDING RADIUS