Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLANK OPEN BREAKER POSITIONS IN PANEL, LABEL BREAKERS |
|
| 11/10/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS 2) BATHROOM RECEPTS TO BE GFI PROTECTED 3) INSTALL SMOKE DETECTORS IN HALL OUTSIDE OF BEDROOMS 4) CLOTHES CLOSET LIGHT TO BE 100 PERCENT ENCLOSED 5) HAVE HAZARDOUS WIRING AT BACK PORCH OUTDOOR BOXES TO BE WEATHER PROOF AND LIGHT FIXTURES TO BE LISTED FOR DAM/WET LOCATION 6) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG SURFACE 7) STRAP METAL FLEX TO WATER HEATER. WATER HEATER TO BE IN WEATHER PROOF ENCLOSURE 8) PANEL TO BE WIRED IN NEAT AND WORKMAN LIKE MANNER. WIRES TOB E PROPERLY SPLICED AND TERMINATED. INSTALL ALL PANEL COVERS AND LABEL ALL BREAKERS. INSTALL BREAKERS LISTED FOR USE IN PANEL 9) VERIFY GROUNDING TYPE RECEPTS ARE PROPERLY GROUNDED. IF NO EQUIPMENT GROUND INSTALL 2 PRONG RECEPTS OR TO BE GFI PROTECTED 10) INSTALL PROPER SIZE FUSE FOR BRANCH CIRCUITS AT FUSE BOX IN CLOSET |