Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE OPEN JUNCTION BOX WITH EXPOSED WIRES IN GARAGE 2) HAVE ROMEX EXPOSED TO PHYSICAL DAMAGE IN GARAGE 3) INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS 4) CHECK HALL SMOKE DETECTOR OPERATIONAL 5) MISSING WALL PLATES 6) PROPERLY WIRE RECEPT MASTER BEDROOM 7) BATHROOM RECEPTS TO BE GFI PROTECTED 8) KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED 9) WIRE HANGING AT BACK PORCH 10) CORD TO RECEPT IN MASTER BATH TO BE REMOVED 11) REMOVE NON CODE COMPLIANT WIRING AT WEST SHED 12) SEAL OPEN KNOCKOUTS AND BREAKER POSITIONS AT SERVICE 13) HAVE ELECTRICAL CONTRACTOR MAKE CORRECTIONS & CHECK WIRING AROUND HOME FOR SAFETY AND MAKE REPAIRS AS NECESSARY |