Permit: T09EL02441

Parcel: 126170690


Addresses:

4004 E HAYNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/01/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/19/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE 1/4" STAINLESS HARDWARE FOR SECURING MAST TO BLDG
2) USE STAINLESS HARDWARE FOR SECURING ONE HOLE STRAPS TO BLDG
3) PROPERLY IDENTIFY NEUTRAL CONDUCTOR TO RANGE
4) ARE COPPER AND ALUMNINUM CONDUCTOR SPLICED TOGETHER FOR RANGE RECPT
5) USE PROPER STAINLESS HARDWARE FOR SECURING PANEL TO BLDG. DO NOT USE SHEETROCK SCREWS
11/17/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL ROOF JACK
2) INSTALL GROUND RODS
3) STRAP MAST TO BLDG
4) BURY GROUNDING ELECTRODE CONDUCTOR
5) FINISH BRANCH CIRCUIT TIE IN AND RECALL