Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/19/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE 1/4" STAINLESS HARDWARE FOR SECURING MAST TO BLDG 2) USE STAINLESS HARDWARE FOR SECURING ONE HOLE STRAPS TO BLDG 3) PROPERLY IDENTIFY NEUTRAL CONDUCTOR TO RANGE 4) ARE COPPER AND ALUMNINUM CONDUCTOR SPLICED TOGETHER FOR RANGE RECPT 5) USE PROPER STAINLESS HARDWARE FOR SECURING PANEL TO BLDG. DO NOT USE SHEETROCK SCREWS |
|
| 11/17/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL ROOF JACK 2) INSTALL GROUND RODS 3) STRAP MAST TO BLDG 4) BURY GROUNDING ELECTRODE CONDUCTOR 5) FINISH BRANCH CIRCUIT TIE IN AND RECALL |