Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02428
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC 2) KO SEAL |
|
| 11/06/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #4 2) INTERIOR OK |
|
| 11/03/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FILL UNUSED OPENING IN PANEL 2) MAINTAIN WORKING CLEARANCES AT PEDESTAL 3) TIGHTEN LOOSE FITTING 4) MAIN BACK FED BREAKER TO HAVE MANUFACTURES HOLDOWN 5) LABEL BREAKERS 6) WEATHER PROOF COVER FOR RECEPTACLE BROKEN 7) ACCESS RAMP IN HAZARDOUS CONDITION 8) NEED INTERIOR ACCESS |