Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02400
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PVC FEEDER CONDUIT TO SHALLOW, MUST BE 24" MINIMUM PER 300.5 NEC 2) SCREW MISSING FOR SUB PANEL COVER ALSO FILL IN BLANKS 3) 110V CONV. RECEPTS MUST BE GFI PROTECTED PER CODE 4) EXPOSE WIRING AT S.E. CORNER |
|
03/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* GATE LOCKED RECALL INSPECTION |
|
01/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PAPERWORK FOR VIOLATION 2) CONDUIT COVERED PRIOR TO INSPECTION 300.5 3) OPEN EQUIPMENT FOR INSPECTION 4) GROUNDING ELECTRODE SYSTEM REQUIRED FOR SEPERATE BLDG 250.34 NEC 5) HAZARDOUS WIRING THRU-OUT BLDG (BACK) |