Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/07/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) SERVICE WIRES, GROUNDING AND BONDING OK 2) CALL BACK FOR FINAL 3) NEED TO SEE BRANCH CIRCUIT |
|
| 11/13/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) NEED RISER BRACED WITH LISTED KIT 2) NEED CONNECTOR FOR GROUNDING ELECTRODE WHERE IT ENTERS PANEL 3) NEED NEUTRAL PHASED 4) NEED ADDRESS ON METER BASE 5) NEED PANEL SCHEDULE 6) NEED WATER AND GAS BONDED 7) GROUNDING RODS OK |