Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09EL02376

Parcel: 126062700


Addresses:

4218 E TEXAS CI

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/17/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/07/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) SERVICE WIRES, GROUNDING AND BONDING OK
2) CALL BACK FOR FINAL
3) NEED TO SEE BRANCH CIRCUIT
11/13/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) NEED RISER BRACED WITH LISTED KIT
2) NEED CONNECTOR FOR GROUNDING ELECTRODE WHERE IT ENTERS PANEL
3) NEED NEUTRAL PHASED
4) NEED ADDRESS ON METER BASE
5) NEED PANEL SCHEDULE
6) NEED WATER AND GAS BONDED
7) GROUNDING RODS OK