Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO POWER TO BE RELEASED. NEED TO MEET WITH LEE RAY TO GET COMBO PERMIT AND CONSOLIDATE ALL OTHER PERMITS. LEE RAY #909-5154 |
|
| 11/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) LOCKED, NO ACCESS |
|
| 12/09/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL PREVIOUS INSPECTION ITEMS FOR BOTH PERMITS |
|
| 10/23/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO SERVICE DISCONNECT IN SERVICE PANEL 2. WAS PANEL REPLACED WITH PERMIT & INSPECTIONS? 3. VERIFY PERMITS FOR ROOF TOP UNIT & WATER HEATER 4. INSTALL NEW GROUNDING ELECTRODE SYSTEM. BOND PIPING SYSTEMS. 5. BOND SERVICE RACEWAYS PER NEC 250.92 6. WIRING IN PANEL APPEARS TO BE DAMAGED 7. WIRE PANEL IN NEAT & WORKMANLIKE MANNER. 8. NEED PANEL DIRECTORY 9. USE 1/4" STAINLESS HARDWARE FOR STRAPPING OF MAST. 10. SEAL OPEN KNOCKOUTS. 11. INSTALL BREAKERS LISTED FOR USE IN PANEL. 12. PROPERLY STRAP SECURE ALL RACEWAYS 13. NEED MIN 6" ???? CONDUCTOR LENGTH @ SPIKES. 14. REMOVE PLANTS FROM IN FRONT OF PANEL. |