Permit: T09EL02300

Parcel: 10120026E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/19/2010 ELECTRIC - FINAL Approved
11/09/2009 ELECTRIC - FINAL Partial Approval ADD 4151 N. CASA GRANDE HY TO THIS PERMIT FOR RELEASE OF POWER TO THIS SERVICE
11/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTES LAST INSPECTION
10/30/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE HOLDOWN PER 408.36 F NEC FOR BACK FED CIRCUIT BREAKERS
2) OPEN INGROUND J-BOX FOR INSPECTION
10/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) U.G. SPLICES TO BE LISTED FOR WET LOCATION GROUND METAL COVER PER 250 NEC
2) SUPPORT OR STRAP #4 TO STRUCTURE
3) USE PROPER SIZED CKT. BREAKERS AT SUB PANELS
4) USE APPROVED HOLDOWN FOR BACK FED MAIN BREAKER