Permit: T09EL02293

Parcel: 140240340


Addresses:

1475 E GANLEY RD

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/17/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/05/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEED PERMANENT METAL ADDRESS LABEL
2) VERIFY TEP RISER REQUIREMENTS
3) USE APPROVED STRAPS AND HARDWARE FOR RISER SUPPORTS SPASE AS PER CODE
4) IDENTIFY NEUTRAL AT WEATHER HEAD
5) PLEASE VERIFY 2ND GROUND ROD
6) USE APPROVED FITTING OR NIPPLE TO POWER OUTLET
7) INSTALL CORD CAP CORRECTLY
8) LABEL BREAKERS
9) IDENTIFY NEUTRAL IN METER SOCKET