Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/28/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOX TO SUPPORT FIXTURE RATED OVER 6 POUNDS 2) BOX NEEDED AT LIGHT FIXTURES |
|
| 01/26/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) KITCHEN RECEPTS TO BE GFCI PROTECTED 2) BOXES MORE THAN 1/4" 314.20 3) USE APPROVED HARDWARE 4) PROTECT BULBS IN CLOSETS 5) MAKE UP EXHAUST FAN AND INSTALL 6) CONNECTOR NEEDED AT LIGHT BOXES AND GROUND BOX 7) PROPERLY LABEL PANEL 408.4 8) ANTI TIP NEEDED FOR RANGE 9) HEAT NEEDED FOR MINIMUM HOUSING |
|
| 12/18/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |