Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2010 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 12/18/2009 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* | |
| 12/11/2009 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) finish previous items #2,3,5,6,7 A REFEE MAY BE ASSESSED. |
|
| 12/08/2009 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) INSTALL GROUNDING ELECTRODE SYSTEM, GAS AND WATER BONDS 3) VERIFY PERMITS FOR NEW NM CABLES AND WIRING 4) MAINTAIN WORKING CLEARNACE IN FRONT OF SERVICE 5) SUPPORT RISER ABOVE PANEL 6) A LISTED MAST BRACE KIT IS NEEDED 7) ANTI-OXIDE COMPOUND IS NEED FOR ALUMNINUM CONDUCTORS 8) MISSING DEAD FRONT COVER |
|
| 11/10/2009 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) GATE LOCKED, NO ACCESS |