Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ALL ITEMS FROM 10-13 INSPECTION. HAVE QUALIFIED ELECTRICAL CONTRACTOR GO THROUGH HOUSE AND GARAGE TO MAKE CORRECTIONS AND REPAIR OR REPLACE NON-CODE COMPLIANT WIRING. INSPECTIONS WITH NO PROGRESS WILL RESULT IN A REINSPECTION FEE |
|
| 10/13/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL OUTDOOR LIGHT FIXTURE AT FRONT DOOR 2) REMOVE EXTENSION CORD FRONT PANEL 3) RECEPTACLE BOX FOR SWAMP COOLER TO BE WEATHER PROOF 4) SERVICE TO BE UPGRADED. INDOOR REATED BOX INSTALLED OUT DOORS 5) OUTDOOR RECEPTACLES TO BE GFI PROTECTED AND NEED WEATHER PROOF COVERS 6) WIRING TO GARAGE TO BE REMOVED OR INSTALLED TO CODE 7) OUTDOOR WIRING TO BE INSTALLED PER CODE OR REMOVED 8) MISSING RECEPTACLE PLATES 9) KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 10) REMOVE NON CODE COMPLIANT LIGHT FIXTURE AT KITCHEN SINK 11) RECEPTACLES HANGING OUT OF WALLS 12) EXPOSED/DAMAGED WIRING AT CEILING FAN KITCHEN 13) MISSING SWITCH PLATES 14) REMOVE 2 WIRE CORD TO CLOSET LIGHTS. REMOVE LIGHTS OR INSTALL PER CODE. INCANDESCENT CLOSET LIGHTS TO BE 100 PERCENT ENCLOSED 15) BATHROOM RECEPTS TO BE GFI PROTECTED 16) INSTALL SMOKE DETECTORS IN BEDROOMS AND OUTSIDE BEDROOM PER INSTRUCTIONS 17) HAVE QUALIFIED ELECTRICAL CONTRACTOR GO THRU HOUSE AND GARAGE. MAKE CORRECTIONS AND REPAIR OR REPLACE NON CODE COMPLIANT WIRING |