| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/04/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/14/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OBTAIN SERVICE UPGRADE PERMIT AND UPGRADE AS NECESSARY-ONE SERVICE HAS BEEN DEMO'ED 2) REMAINING SERVICE IS NOT RATED FOR OUTDOOR USE. CONNECTIONS ON ROOF AT POA NOT TO CODE, SOMEONE CUT SERVICE RISER CONDUCTORS OFF FOR OTHER SERVICE, NOT RE-WRAPPED PROPERLY 3) CONDUIT CONNECTOR AT BOTTOM OF SERVICE DISCONNECT NOT CORRECT FOR APPLICATION |