Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02255
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/17/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTE #3 LAST INSPECTION |
|
| 11/13/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL MAIN BONDING JUMPER 2) TERMINATE GROUNDING ELECTRODE CONDUCTOR 3) BOND SERVICE RISER 4) INSTALL LABELING PER INSTRUCTIONS 5) NO PLANS ON SITE |