Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02255
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/17/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTE #3 LAST INSPECTION |
|
11/13/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL MAIN BONDING JUMPER 2) TERMINATE GROUNDING ELECTRODE CONDUCTOR 3) BOND SERVICE RISER 4) INSTALL LABELING PER INSTRUCTIONS 5) NO PLANS ON SITE |