Permit: T09EL02251

Parcel: 136282200

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/19/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/14/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL OPENING IN BACK OF PANEL AT WIRE ENTRY WITH NON-COMBUSTIBLE MATERIAL
2) BOND NIPPLE BETWEEN PANEL AND METER NEC 250.92 & 250.102
3) BOND SERVICE RISER NEC 250.92 & 250.102
4) SERVICE ENERGIZED PRIOR TO APPROVAL