Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK GROUND RODS 2) OK GAS AND WATER BOND 3) RECALL AFTER SWING OVER COMPLETE |
|
| 10/06/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO OBTAIN PERMITS FOR ALL NEW WORK. PROVIDE APPROVED PLANS AND PERMITS. CLEARANCE WILL NOT BE SENT TO TEP UNTIL PERMITS OBTAINED 2) GROUND RODS TO BE MINIMUM 6' APART 3) MINIMUM SERVICE CONDUCTOR CLEARANCE OVER RESIDENTIAL PROPERTY IS 12' 4) THIS INSPECTOR HAS WITNESSED NEW WORK BEING DONE TO HOME INCLUDING KITCHEN REMODEL |