Permit: T09EL02207

Parcel: 106090110


Addresses:

1635 W ROGER RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09EL02207

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/21/2010 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/17/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK #24 & 25 U.G.
06/11/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) CONDUITS TO PEDESTALS 15,16,17,20,21,26,27 & 28 OK
2) CROSSING AT 21 OK TO GROUP OF 5 DISCONNECTS BEHIND
3) CONDUITS TO BOX LOCATION IN FRONT OF 27 OK
4) REMAINDER OF CONDUIT TO PED 22 OK
06/04/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) READ X-ING BETWEEN #27-21 OK
2) 3-2" PVC OK BETWEEN DISCONNECTS AND PULL BOX LOCATION (SEE NOTE #2 ON S/26)
3) 1-1 1/2 PVC OK FROM DISCONNECTS TO PATIO OF UNIT #15 IN FRONT OF SOUTH DOOR
4) KEEP IN MIND CONDUCTOR BEND REQUIREMENTS IN PULL BOX
05/26/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) THREE (3) 2" PVC OK TO COVER FROM SERVICE M.1 TO NORTH END OF UNIT #5
2) PROVIDE PULL BOX TO AVOID EXCESSIVE BENDS TIN RUN TO DISCONNECT LOCATION, YET TO BE TRENCHED AND INSPECTED
05/04/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) UNIT #22 PEDESTAL TO FENCE
04/30/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK CONTINUE U.G. AT UNIT #2 TO PANEL "B", #6 & 8
2) OK COMPLETION U.G. AT #29 & 30
04/19/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PROGRESS NOW BEING MADE ON OUTSTANDING ISSUES. INSPECTIONS TAKING PLACE
2) 1 1/2" AND 2" PVC OK FOR CIRCUITS B-10 & 12 UNDER ROAD TO:
3) #19, #18 PED. AND RV. #29 OK TO FRONT PORCH, #31 OK FROM PED. TO SOUTH SIDE OF DRIVE
04/09/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. ONLY 2" & 1 1/2" FEEDERS FROM SERVICE #B UP TO UNIT #3 AND DRIVEWAY #45 TO DISCONNECTS
2) MUST REOPEN EXPIRED PERMIT #T06EL01371 AND CALL IN INSPECTION AFTER WORK COMPLETE
3) NO FUTURE INSPECTIONS WILL BE PERFORMED UNTIL PROGRESS MADE CONCERNING CODE VIOLATIONS RELATED TO PHASE ONE, UNIT 1 THRU 15
4) PERMIT #T10EL00639 PEDESTALS INSTALLED PRIOR TO INSPECTION AND EQUIPMENT NOT INSTALLED PER LISTING 110.3 AND 300.4 NEC
5) EXPOSE WORK PREVIOUSLY COVERED, MAKE CORRECTIONS AS NECESSARY-CALL FOR INSPECTION
04/07/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. NO PROGRESS MADE TO RESOLVE ISSUES RELATED TO WORK AT PHASE ONE OF PROJECT
2. OK U.G ONLY AT 36, 37, 32, 33, 34
04/01/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. CONDUIT ONLY (1 1/2" AND 2") FOR 51,47,50,48,49,39,40,40A AND 35
2) OK PULL BOX AT 45
3) #36 ALMOST DONE-OK TO PUT PEEP HOLES
4) NO PAST PEEP HOLES INSPECTED
03/22/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G. CONDUIT ONLY FOR 45, 46, 56, 58, 53, 38, 52
03/19/2010 ELECTRIC - UNDERGROUND Cancelled CANCELLED PER DAVID OF MEHL ELECTRIC #237-3133
03/16/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK UNITS U.G. ONLY FOR 1 1/2 AND 2" PVC, NO GROUNDING OR PEDESTALS, #41,42,43,44,54,55 & 57
11/19/2009 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) ROAD CROSSING COVERED PRIOR TO INSPECTION
2) SEE NOTES LAST INSPECTION
3) COMMENT BY OWNER OF ELECTRICAL CONTRACTOR "I CAN ACCEPT THE PICTURES OR BE TAKEN OFF THE JOB" READ CROSSING IS DEEP ENOUGH BECAUSE I SAID SO
11/13/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) CONDUIT TO SHALLOW AT UNITS #4-5 AND AROUND #10 SEE 300.5, OTHER AREAS SUCH AS ROAD CROSSING AND PARKING MUST BE 24"