Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02206
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ITEMS ON LIST OK |
|
10/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED #6 AND LARGER TO BE STRANDED, IF #6 MUST BE GREEN COLOR INSULATION, 250-119 2) INSTALL BUSHINGS ON 1 1/2" CONDUIT TERMINATION FOR #4 OR LARGER 3) PLANS CALL FOR 42/10 AIC CIRCUIT BREAKERS 4) PLAN SHOWS 600 AMP SECONDARY FEEDERS AND THE EXISTING IS 350 MCM AL-250 AMPS |
|
10/05/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) VERIFY GROUNDING ELECTRODE SYSTEM IS INTACT OR USE 2 GROUND RODS, WORK NOT COMPLETE, GROUNDING AND BONDING, FEEDERS, SECONDARYS NOT TERMINATED YET |