Permit: T09EL02201

Parcel: 107082000

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/04/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO LAST WRITE-UPS ON SITE
1. VERIFY DERATING OF CONDUCTORS 310.15 + 310.16
2. ONLY ONE GROUNDED CONDUCTOR PER TERMANAL LUG
3. SUPPORT CONDUITS PER CODES
4. BOND JUNCTION BOXES
01/20/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) LABEL FUSES IN PANEL, SHOULD BE #10 SIZE CONDUCTORS ON 30 AMP FUSES, NO DBL LUGGING
2) ADVISED HOMEOWNER WATER HAS BEEN LEAKING INTO OLD SERVICE EQUIP. ADVISED TO UPGRADE SOON
3) AREA IN FRONT OF SERVICE TO BE KEPT CLEAR
4) RECALL INSPECTION