Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES PERTAIN TO 2158 & 2160 N. RITA AVE: 1) GROUNDING ELECTRODE SYSTEMS SHALL BE COMMON WHEN MORE THAN 1 SERVICE ON BLDG 250.58 NEC 2) MUST USE A LISTED RISER SUPPORT ON ROOF-HOMEMADE OUT OF EMT SMASHED AT ENDS-NOT APPROVED 3) #10 WOOD OR SHEET METAL SCREWS NOT APPROVED FOR RISER SUPPORT, USE MINIMUM 1/4" LAGS OR ANCHORS 4) TEK SCREWS NOT APPROVED FOR GROUNDING IN J-BOXES 250.8 NEC. DO NOT USE NEUTRALS TO BODN 250.6 NEC 5) VERIFY GAS AND WATER PIPE BONDING 6) SERVICES RE-ENERGIZED PRIOR TO INSPECTOR CLEARANCE |